With their intuitive graphics interface, AXRON products are easy to use. Clear functions with texts and alarms in the client’s language, facilitate familiarisation, the wide opening simplifies integration and their extensive modular system guarantees they will evolve over time.
FUNCTIONALITIES
Temperature-controlled by PID (cascade).
%C controlled with O2 probe and CO-CO2 analyzer.
On-line calculation of the part’s carbon distribution profile, effective depth and surface carbon.
Flexible programming of processing profiles with recipe library; stop-start on weekly schedule and deferred start to processing.
Management of peripherals: coolers, analyzers, quenching tank. Loading and unloading system control, automation of the quenching system, with secured manual control systems.
Calibration of the measuring instrument and sensors (AT) and calibration of the heating chamber (TUS).
Specific screens for capturing production monitoring information.
“T” models provide process value archiving (.CSV format) on detachable storage medium (USB) and on a network drive; PC software for graphic display of files generated can be supplied with the device.
SERVICES AND ADD-ONS
On-site electrical and mechanical integration.
On-site commissioning and training.
Risk analysis, compliance.
Thermal mapping (TUS), analysis of the reactor’s atmosphere.
Remote access, maintenance agreements.
Back-up and remote data archiving.
Optimisation of heat rating.
Automation of the quenching sequence.
Integration with ERP or SCADA, centralisation of recipes and/or archive data.
Installation of Remote Viewers (TCP/IP).
Can be connected to bar code readers.
BENEFITS
Easy: User-friendly and intuitive, lively overview diagrams, multi-lingual screens, clear alarms.
Scalable: Extensible and modular hardware/software.
Standard: Based on the latest industrial standards, 100% Siemens contract hardware.
Open: Easily integrated with ERP, SCADA.
Accurate : ±0.1% for thermocouples
Safe: Process safety systems.
FEATURES
Multi-segment programmer that can store up to 100 processing profiles.
Up to 16 PID control loops, cascade or master-slave. ON-OFF control or power controller (thyristor).
%C controlled with O2 probe or scanner with independent PIDs; dual %C calculation (CO-O2 and CO-CO2) and probe monitoring for comparison; %CSat calculated and controlled (soot and carbide limit); %CO controlled by modulating the proportion of CHx-N2. ON-OFF control or with mass flow rates.
Extensible and modular Hot-Swap inputs/outputs. TCP/IP, Profibus or Profinet communication.
Management of process safety systems, monitoring of the injection temperature per redundant system, N2 purges, gas ignition, flow rate and pressure monitoring.
TECHNICAL SPECIFICATIONS
Environmental conditions
Assembly position: Vertical
Working temperature: 0°C to +50°C
Storage temperature: -20°C to +60°C
Max. relative humidity of the air: 90%
Protection: IP65, NEMA 4, NEMA 4x, NEMA 12
Supply
Supply voltage: 24V DC
Admissible range: +19.2V to +28.8V DC
Rated screen current: From 0.2A (380K) to 1.5A (1210T)
Controller ringing current: 1.8A
Models | 380K | 430K | 750T | 1210T |
Type of screens | TOUCH, STN, grey levels | TOUCH, TFT, 256 colors | TOUCH, TFT, 65536 colors | |
Type of keyboards | Membrane, 4 keys | Only TOUCH * *Also available with keyboard (KEY) | ||
Size, resolution (pixels) | 3.8’’ (320x240) | 4.3’’ (480x272) | 7.5’’ (640x480) | 12.1’’ (800x600) |
Dim. front (LxH) | 140x116 mm | 140x116 mm | 240x180 mm | 335x275 mm |
Dim. cut-out (LxH) | 123x99 mm | 123x99 mm | 226x166 mm | 310x248 mm |
Depth | 40 mm | 48 mm | 60 mm | 72 mm |
Weight | 0.32 kg | 0.50 kg | 1.61 kg | 3.80 kg |
Interfaces | TCP/IP - - | TCP/IP USB MMC | TCP/IP 2xUSB MMC | 2xTCP/IP 2xUSB CF, MMC |
Furnaces (std/max) | 1/1 | 1/1 | 1/2 | 1/3 |
PID ctrl loops (std/max) | 3/6 | 4/8 | 4/12 | 4/16 |
Programs (std/max) | 10/20 | 20/40 | 25/50 | 50/100 |
Barcode reader | No | Yes | Yes | Yes |
Archives | No | No | Yes | Yes |
PC Soft | ECO PCS-P | ECO PCS-P | ECO PCS-P/A | ECO PCS-P/A |
Controller and I/O:
Siemens IM151-8 PN/DP controller with MMC for saving the program.
I/O Siemens ET200S (Hot Swap), High Feature for thermocouples, accuracy to ±0.1%.
Certifications / standards:
CE, UL, cULus, C-TICK, FM Class I Div. 2, NEMA 4, NEMA 4x, NEMA 12.
Compatibility (CEM):
Emissions (pursuant to EN55 011): EN 61000-6-4.
Designed for use in an industrial environment.
AXRON Swiss contact
Jean-Claude Stehlin
Area Sales Manager
Dec. 2011
Aucun commentaire: